Intelligent Nickel-Zinc Battery Cabinet
BC-3830S15BA0
Intelligent Nickel-Zinc Battery Cabinet
Key Features:
- High reliability: Open-circuit-free discharge performance
- Ultimate safety: Pass extreme tests e.g. axe chopping, drilling, heavy crushing, fire exposure with zero fire or explosion, significantly exceeding traditional battery safety standards
- Wide Temperature Range: Maintain stable performance and high efficiency in extreme environments (-20°C to 55°C), surpassing traditional battery temperature limits
- Medium discharge rate: Support 1C-3C discharge rates, balancing capacity and power requirements for diverse application scenarios
- Eco-friendly: Utilize non-toxic materials with >90% recyclability, enabling clean energy closed-loop systems for low-carbon development

Technical Parameters
Product Specifications
Complete technical data for the BC-3830S15BA0 Nickel-Zinc Battery Cabinet.
| Parameter | Result |
|---|---|
| TECHNICAL PARAMETER: BC-3830S15BA0 | - |
| Technical parameter | BC-3830S15BA0 |
| Rated voltage | 396VDC |
| Charging voltage range | Float charge 444VDC, equalization charge 456VDC |
| Min & max charging current | Min 11.4A, max 38A |
| Fast charging current | 38A |
| Standard charging | 11.4A CC/CV charging to 15.20V, switch to CV charging until cut-off at 3.8A |
| Battery nominal capacity | 38Ah (38A discharge to 10.4V, 25°C) |
| Cabinet power | 15kWh |
| Max discharging current | 190A |
| Battery string configuration | 30 batteries/string/cabinet (30S1P) |
| Monitoring | Standard: cell voltage, cell & ambient temperature, charge/discharge current, cell IR, float current, SOC/SOH |
| Monitoring | Optional: string voltage, ripple current, ripple voltage, ground insulation, H 2 concentration, thermal runaway early warning, liquid level, leak analysis & localization |
| Protection function | Overcharge/overdischarge/overcurrent alarm |
| Data communication | Ethernet, RS485 |
| Safety | UL 9540A certified, no thermal runaway |
| Circuit breaker protection | Automatically cuts off current upon fault detection to protect battery safety |
| Operating temperature range | -20°C~+55°C |
| Storage temperature range | -20°C~+55°C |
| Storage period | Recharge required after storage exceeding 6 months at 25°C |
| Humidity range | 0~90%RH, no condensation |
| Cooling | Air cooling |
| Transportation | No shipping restrictions |
| Battery | UL 9540A, RoHS |
| EU battery directive | UL9540A, RoHS, TTL, EU2023/1542 |
| Dimension(WDH) | 600mm700mm2000mm |
| Weight | 450kg |
Scroll to view all parameters ↕