680kW/48U
680kW/48U
The 680 kW CDU is a liquid cooling unit that removes heat generated by equipment through the secondary-side heat exchange via a plate heat exchanger, and transfers the heat away through the primary-side chilled water loop.
Key Features:
- Pump Redundancy: Adopts an N+1 pump configuration with cyclic switchover, ensuring continuous operation in case of single pump failure.
- High Cooling Capacity In a Compact Footprint: Features a highly integrated piping design, with a footprintof only 1200 x 600 mm (LxW), and is capable of removing up to 680 kW of heat.
- Easy Maintenance Access: The electrical control cabinet adopts a tiltable structure. During maintenance, such as removing filter elements orreplacing pumps, the cabinet can be lifted via hydraulic supports, providing sufficient operating space.
- Flexible Movement and Handling: Equipped with four heavy-duty casters at the base. The bottom structure allows for forklift handling for easy loading, and also enables flexible movement on the floor for convenient repositioning.

Technical Parameters
Product Specifications
Complete technical data for the 680kW/48U L2L In-Row CDU.
| Parameter | Result |
|---|---|
| TECHNICAL PARAMETERS: 680KW / 48U / L2L CDU | - |
| Technical parameters | 680kW / 48U / L2L CDU |
| Rated cooling capacity | 680 kW @ 4.0°C ATD |
| Maximum flow rate – single pump operation | 700L/min, external pressure difference 2.0bar |
| Maximum flow rate – dual pump operation for N+ redundancy | 1050L/min, external pressure difference 3.4bar |
| Secondary coolant type | Pure Water or PG25 |
| Pump redundancy | Single pump (N) / dual pump (N+N) / dual pump switchover |
| Primary pressure drop | 0.8 bar (PG25) under typical conditions (650 L/min) |
| Secondary coolant temperature range | 10–55°C, with dew point control standard |
| Maximum power consumption | 4.5 kW (Single Pump) 7.3 kW (Dual Pump) |
| Dimensions (H × W × D) and weight | 1900 × 600 × 1050 mm, 550 kg |
| Noise level at 3m (10ft) | < 54 dBA |
| Power supply (Europe, Asia and Taiwan) | 3P 380-480 V 50/60 Hz |
| Dual power supply (ATS) | Optional features |
| Primary connections | Top or bottom, 2½-inch sanitary flange |
| Secondary connections | Top or bottom, 2½-inch sanitary flange |
| Secondary filtration | Optional 50um/20um |
| Communication | RS485 RTU modbus, TCP/IP SNMP |
Scroll to view all parameters ↕