850kW

850kW

Direct Liquid Cooling Container The 850 kW system integrates secondary-side heat sources, CDU, and primary-side dry cooler within a standard 12 m container, forming a complete cooling system. Users can place the equipment requiring cooling directly inside the container. The system operates with power supply only, and the standardized container dimensions significantly reduce layout complexity.

Key Features:

  • Integrated Container System: Integrates heat load equipment, CDU, and dry cooler. A single container functions as a small-scale workshop with a high level of integration.
  • Minimal Infrastructure Requirement: Requires only power supply for operation. Only needs to consider power cable routing, and the standardized container dimensions significantly reduce layoutdifficulty in the facility.
  • Active Fluid Management & Pump Redundancy: Equipped with an expansion tank and make-up tank. When system pressure reaches the set value, automatic coolant replenishment is performed. The make-up tank is equipped with a liquid level sensor, which triggers an alarm when the level drops below a certain threshold, allowing timely maintenance and ensuring normal system operation. In addition, the CDU adopts an N+1 pump cyclic operation mode, further enhancing system stability.
  • Configurable Internal Layout: The system supports customized design based on different heat-generating components, enabling different rack configurations. Supports the integration of secondary-side heat sources, CDU, and primary-side dry cooler within a single container, forming a mobile small-scale workshop.
Technical Parameters

Product Specifications

Complete technical data for the 850kW Direct Liquid Cooilng Container.

ParameterResult
TECHNICAL PARAMETERS: 850KW / DIRECT LIQUID COOLING CONTAINER-
Technical parameters850kW / Direct Liquid Cooling Container
Rated cooling capacity850kW
Dimensions (L × W × H)12192mm × 2438mm × 2896mm
Operating weight (t)19
Coolant volume (L)2000
Reference load typeGB300
Number of racks6
Input voltage3P 380-480V 50/60Hz
Output voltageSingle-phase 200-277V 50/60Hz
Power supplySmart PDU × 6
Cooling typeClosed-loop cooling tower / Dry cooler
Inlet temperature (° C)45
Outlet temperature (° C)60
Design reference temperature (° C)35
CommunicationHMI, SNMP, Modus
Scroll to view all parameters ↕